Bubba Moore
Technical Services Manager
Southeast District
Measuring Airflow Using Temperature Rise Method
What is airflow in a heating and cooling system? Why do we need to know what the airflow of a heating or cooling system is? Airflow is the amount of air measured in cubic feet per minute (CFM) that a system can deliver or move depending on its size. This CFM of a system is normally around 400 to 450 CFMs per ton of air. This can vary depending on the efficiency of the system. The reason we need to know the airflow of the system is to make sure that the system is performing as it was designed. Too much or too little airflow can affect comfort and cause equipment failures.
There are different methods of measuring airflow. The temperature rise method is fairly easy to use when measuring the CFMs on fan coils with electric heat. You will measure the amount of temperature rise across the electric heat elements, and also measure the voltage supplying the system, as well as the current flow or amps of the fan coil. The fan coil blower and electric elements will have to run continuously while preforming these measurements. Before taking any temperature readings or other measurements, make sure that the air filter is clean, and that all supply and return vents are opened and not blocked. Also, let the system run until the temperatures stabilize. Once the temperatures stabilize, measure the return air and supply air temperatures with an accurate electronic thermometer. Do not get your temperature reading above the electric elements. Make sure that these readings are down the duct or out of the line of sight of the electric elements.
After the measurements have been gathered, this data will be plugged into a formula to see what airflow (CFMs) the system is producing. The formula is: Airflow (CFM) equals volts times amps times 3.414 (BTUs per watt) divided by 1.08 times the temperature difference of the supply and return air.
Using 400 CFMs per ton, this airflow calculation would be close to 3 Tons of airflow.
This simple calculation could help prove whether or not the problem is related to airflow. There may be a collapsed duct, or insulation inside of the duct may have come loose. If there was an equipment failure, this CFM test could prove why the equipment failed. It could also prove that airflow was not the problem and help point to a different reason for the failure.
Sources: HVAC Services Procedures
More to explore
Veto Promo
April 2024 Veto Pro Pac Promotion Check out the video and resources below to take advantage of our April Veto bag promotion.
2024 Mingledorff’s Dealer Meeting
There is no excerpt because this is a protected post.
Black History Month
Black History Month takes place between February 1st and March 1st every year. It’s a time to celebrate and observe the accomplishments,
Keep up to date with the latest HVAC news from Mingledorff’s Inc.